About cookies on this site Our websites require some cookies to function properly (required). In addition, other cookies may be used with your consent to analyze site usage, improve the user experience and for advertising. For more information, please review your options. By visiting our website, you agree to our processing of information as described in IBM’sprivacy statement. To provide a smooth navigation, your cookie preferences will be shared across the IBM web domains listed here.
Paper
Summit and Sierra supercomputer cooling solutions
Abstract
Achieving optimal data center cooling efficiency requires effective water cooling of high-heat-density components, coupled with optimal warmer water temperatures and the correct order of water preheating from any air-cooled components. The Summit and Sierra supercomputers implemented efficient cooling by using high-performance cold plates to directly water-cool all central processing units (CPUs) and graphics processing units (GPUs) processors with warm inlet water. Cost performance was maximized by directly air-cooling the 10% to 15% of the compute drawer heat load generated by the lowest heat density components. For the Summit system, a rear-door heat exchanger allowed zero net heat load to air; the overall system efficiency was optimized by using the preheated water from the heat exchanger as an input to cool the higher power CPUs and GPUs.