Publication
ITherm 2006
Conference paper

Direct liquid jet-impingement cooling with micronsized nozzle array and distributed return architecture

View publication

Abstract

We demonstrate submerged single-phase direct liquid-jet-impingement cold plates that use arrays of jets with diameters in the range of 31 to 126 μm and cell pitches from 100 to 500 μm for high power-density microprocessor cooling applications. Using parallel inlet and outlet manifolds, a distributed return concept for easy scaling to 40,000 cells on an area of 4 cm2 was implemented. Pressure drops < 0.1 bar at 2.5 1/min flow rate have been reached with a hierarchical tree-like double-branching manifold. Experiments were carried out with water jets having Reynolds numbers smaller than 900 at nozzle to heater gaps ranging between 3 to 300 μm. We identified four flow regimes, namely, pinch-off, transition, impingement, and separation, with different influences on heat-removal and pressure-drop characteristics. Parametric analysis resulted in an optimal heat-removal rate of 420 W/cm 2 using water as a coolant. For a near optimal design with a gap to inlet diameter ratio of 1.2, we measured a heat-transfer coefficient of 8.7 W/cm2K and a junction to inlet fluid unit thermal resistance of 0.17 Kcm2/W (720 μm chip), which is equivalent to a 370 W/cm 2 cooling performance at a junction to inlet fluid temperature rise of 63°C, a pressure drop of 0.35 bar, and a flow rate of 2.5 1/min. © 2006 IEEE.